AWG Wire Gauge Chart
Diameter, cross-section and resistance for every American Wire Gauge size, with the NEC ampacity of building wire and a metric converter.
AWG numbers fall as wire gets thicker. 12 AWG is 2.05 mm across (3.31 mm²) and 10 AWG is 2.59 mm (5.26 mm²). Every 3 gauges doubles the copper area; every 6 gauges doubles the diameter.
AWG ↔ mm² converter
American Wire Gauge chart, 4/0 to 40 AWG
| AWG | Diameter (in) | Diameter (mm) | Area (mm²) | Area (cmil) | Copper Ω/1000 ft @20 °C |
|---|---|---|---|---|---|
| 4/0 | 0.4600 | 11.684 | 107.22 | 211,600 | 0.0490 |
| 3/0 | 0.4096 | 10.405 | 85.03 | 167,806 | 0.0618 |
| 2/0 | 0.3648 | 9.266 | 67.43 | 133,077 | 0.0779 |
| 1/0 | 0.3249 | 8.251 | 53.48 | 105,535 | 0.0983 |
| 1 | 0.2893 | 7.348 | 42.41 | 83,693 | 0.1239 |
| 2 | 0.2576 | 6.544 | 33.63 | 66,371 | 0.1563 |
| 3 | 0.2294 | 5.827 | 26.67 | 52,635 | 0.1970 |
| 4 | 0.2043 | 5.189 | 21.15 | 41,741 | 0.2485 |
| 5 | 0.1819 | 4.621 | 16.77 | 33,102 | 0.3133 |
| 6 | 0.1620 | 4.115 | 13.30 | 26,251 | 0.3951 |
| 7 | 0.1443 | 3.665 | 10.55 | 20,818 | 0.4982 |
| 8 | 0.1285 | 3.264 | 8.37 | 16,510 | 0.6282 |
| 9 | 0.1144 | 2.906 | 6.63 | 13,093 | 0.7921 |
| 10 | 0.1019 | 2.588 | 5.26 | 10,383 | 0.9988 |
| 11 | 0.0907 | 2.305 | 4.17 | 8,234 | 1.26 |
| 12 | 0.0808 | 2.053 | 3.31 | 6,530 | 1.59 |
| 13 | 0.0720 | 1.828 | 2.62 | 5,178 | 2.00 |
| 14 | 0.0641 | 1.628 | 2.08 | 4,107 | 2.53 |
| 15 | 0.0571 | 1.450 | 1.65 | 3,257 | 3.18 |
| 16 | 0.0508 | 1.291 | 1.31 | 2,583 | 4.02 |
| 17 | 0.0453 | 1.150 | 1.04 | 2,048 | 5.06 |
| 18 | 0.0403 | 1.024 | 0.82 | 1,624 | 6.38 |
| 19 | 0.0359 | 0.912 | 0.65 | 1,288 | 8.05 |
| 20 | 0.0320 | 0.812 | 0.52 | 1,022 | 10.15 |
| 21 | 0.0285 | 0.723 | 0.41 | 810 | 12.80 |
| 22 | 0.0253 | 0.644 | 0.33 | 642 | 16.14 |
| 23 | 0.0226 | 0.573 | 0.26 | 509 | 20.36 |
| 24 | 0.0201 | 0.511 | 0.20 | 404 | 25.67 |
| 25 | 0.0179 | 0.455 | 0.16 | 320 | 32.37 |
| 26 | 0.0159 | 0.405 | 0.13 | 254 | 40.81 |
| 27 | 0.0142 | 0.361 | 0.10 | 202 | 51.47 |
| 28 | 0.0126 | 0.321 | 0.0810 | 160 | 64.90 |
| 29 | 0.0113 | 0.286 | 0.0642 | 127 | 81.83 |
| 30 | 0.0100 | 0.255 | 0.0509 | 101 | 103.19 |
| 31 | 0.0089 | 0.227 | 0.0404 | 80 | 130.12 |
| 32 | 0.0080 | 0.202 | 0.0320 | 63 | 164.08 |
| 33 | 0.0071 | 0.180 | 0.0254 | 50 | 206.90 |
| 34 | 0.0063 | 0.160 | 0.0201 | 40 | 260.90 |
| 35 | 0.0056 | 0.143 | 0.0160 | 32 | 328.98 |
| 36 | 0.0050 | 0.127 | 0.0127 | 25 | 414.84 |
| 37 | 0.0045 | 0.113 | 0.0100 | 20 | 523.10 |
| 38 | 0.0040 | 0.101 | 0.0080 | 16 | 659.62 |
| 39 | 0.0035 | 0.090 | 0.0063 | 12 | 831.77 |
| 40 | 0.0031 | 0.080 | 0.0050 | 10 | 1048.84 |
d = 0.005 in × 92(36 − n)/39
area = (1000 × d)² cmil = π ÷ 4 × dmm² mm²
R = 10.371 × 1000 ÷ cmil Ω per 1000 ft (copper, 20 °C)
n is the gauge number, with 1/0 = 0, 2/0 = −1, 3/0 = −2 and 4/0 = −3. Every step of one gauge multiplies the diameter by about 1.123, so six steps double it and three steps double the area. The resistance column is for copper at room temperature; NEC Table 8 lists values at 75 °C, about 21% higher, and that is what the voltage drop calculator on this site uses.
Building wire: ampacity by gauge
For house wiring the question is usually how much current a gauge can carry. The answer depends on the insulation temperature rating and the terminals, which is why NEC Table 310.16 gives three columns. NM-B cable uses the 60 °C column.
| Size | Cu 60 °C | Cu 75 °C | Cu 90 °C | Al 60 °C | Al 75 °C | Al 90 °C | 240.4(D) cap |
|---|---|---|---|---|---|---|---|
| 14 AWG | 15 | 20 | 25 | — | — | — | 15 A |
| 12 AWG | 20 | 25 | 30 | 15 | 20 | 25 | 20 A |
| 10 AWG | 30 | 35 | 40 | 25 | 30 | 35 | 30 A |
| 8 AWG | 40 | 50 | 55 | 35 | 40 | 45 | — |
| 6 AWG | 55 | 65 | 75 | 40 | 50 | 55 | — |
| 4 AWG | 70 | 85 | 95 | 55 | 65 | 75 | — |
| 3 AWG | 85 | 100 | 115 | 65 | 75 | 85 | — |
| 2 AWG | 95 | 115 | 130 | 75 | 90 | 100 | — |
| 1 AWG | 110 | 130 | 145 | 85 | 100 | 115 | — |
| 1/0 AWG | 125 | 150 | 170 | 100 | 120 | 135 | — |
| 2/0 AWG | 145 | 175 | 195 | 115 | 135 | 150 | — |
| 3/0 AWG | 165 | 200 | 225 | 130 | 155 | 175 | — |
| 4/0 AWG | 195 | 230 | 260 | 150 | 180 | 205 | — |
Sizes larger than 4/0 are named in kcmil (thousands of circular mils): 250, 300, 350, 400 and 500 kcmil are the common service and feeder sizes.
Metric cable sizes and the nearest AWG
| Metric size | Exact AWG | Nearest standard |
|---|---|---|
| 0.5 mm² | 20.15 | 20 AWG |
| 0.75 mm² | 18.40 | 18 AWG |
| 1 mm² | 17.16 | 17 AWG |
| 1.5 mm² | 15.41 | 15 AWG |
| 2.5 mm² | 13.21 | 13 AWG |
| 4 mm² | 11.18 | 11 AWG |
| 6 mm² | 9.43 | 9 AWG |
| 10 mm² | 7.23 | 7 AWG |
| 16 mm² | 5.20 | 5 AWG |
| 25 mm² | 3.28 | 3 AWG |
| 35 mm² | 1.83 | 2 AWG |
| 50 mm² | 0.29 | 1/0 AWG |
| 70 mm² | -1.16 | 2/0 AWG |
| 95 mm² | -2.48 | 3/0 AWG |
| 120 mm² | -3.49 | 4/0 AWG |
Which gauge for which job
Typical sizes in US homes and on job sites. They assume copper, short runs and the circuit breaker shown; long runs go one or two sizes up for voltage drop.
| Use | Typical gauge | Notes |
|---|---|---|
| Lamp and appliance cords | 18 or 16 AWG | Cord ampacity follows Table 400.5, not 310.16 |
| Thermostat and doorbell wire | 18 AWG | Class 2 low-voltage, 24 V |
| Light-duty extension cord | 16 AWG | Up to about 10–13 A at 25–50 ft |
| Lighting and general outlets, 15 A | 14 AWG | 14-2 NM-B, white jacket |
| Kitchen, bath, laundry outlets, 20 A | 12 AWG | 12-2 NM-B, yellow jacket |
| Dryer or water heater, 30 A | 10 AWG | 10-3 for dryers with a neutral |
| Cooktop or 40 A charger | 8 AWG | 8 AWG NM-B is a 40 A cable |
| Range, 50 A charger | 6 AWG | 50 amp wire size |
| 100 A subpanel feeder | 3 AWG Cu or 1 AWG Al | At 75 °C, before voltage drop |
| 200 A residential service | 2/0 Cu or 4/0 Al | Using the 310.12 dwelling reduction |
How gauge changes resistance and current
Because area changes by a fixed ratio between gauges, resistance does too: each step down in gauge number cuts resistance by about 20.6%, and each three steps cut it in half. That is why a 10 AWG run has roughly 63% of the resistance of 12 AWG and can carry the same load almost 60% farther for the same voltage drop. Ampacity does not scale so neatly, because a thicker conductor sheds heat through a surface that grows more slowly than its area; this is why the NEC table rises in uneven steps rather than doubling every three gauges.
Solid vs stranded
A stranded conductor of a given AWG has the same total copper area as the solid one, so ampacity is the same and resistance nearly so: NEC Table 8 lists 12 AWG copper at 1.93 Ω/1000 ft solid and 1.98 stranded. Stranded wire is larger in overall diameter and much more flexible, which is why it is required for 8 AWG and larger in conduit under 310.3(C) and preferred for anything that moves or vibrates.
Reading the gauge on a cable
NM-B jackets are color-coded by size in the US: white for 14 AWG, yellow for 12 AWG, orange for 10 AWG, and black for 8 and 6 AWG. The printed legend gives the full story: "12-2 W/G" means two 12 AWG insulated conductors plus a bare ground; "10-3" adds a red conductor for 240 V or multi-wire circuits.
Related calculators and charts
- Wire size calculatorChoose the gauge for a load, distance and voltage.
- Voltage drop calculatorCheck a gauge over your actual run length.
- What size wire for 50 amp6 AWG or 8 AWG, and when to go bigger.
Questions people ask
Why does a smaller AWG number mean a thicker wire?
The gauge number counted the drawing steps used to make the wire. Each pass through a die made it thinner, so a higher number meant more passes and a thinner wire. The modern standard (ASTM B258) fixes 36 AWG at 0.005 in and 0000 AWG at 0.46 in, with 39 equal ratio steps between them.
How thick is 12 gauge wire?
Solid 12 AWG copper is 0.0808 in (2.05 mm) across with an area of 3.31 mm². Stranded 12 AWG has the same copper area but is a little larger overall because of the gaps between strands.
What is the rule of thumb between gauges?
Every 3 gauge numbers doubles or halves the area (and the resistance), and every 6 numbers doubles or halves the diameter. Every 10 numbers changes the area by about 10 times.
Is AWG the same as SWG or mm²?
No. SWG (British Standard Wire Gauge) uses different steps, and most of the world sizes cable by cross-section in mm². Use the metric table on this page to find the nearest AWG size, and pick the larger one when the match is not exact.
Does this chart tell me how many amps a wire can carry?
The full chart gives geometry and resistance only. For building wire, use the ampacity table further down, which comes from NEC Table 310.16 and depends on the insulation temperature rating.