AWG Wire Gauge Chart

Diameter, cross-section and resistance for every American Wire Gauge size, with the NEC ampacity of building wire and a metric converter.

AWG numbers fall as wire gets thicker. 12 AWG is 2.05 mm across (3.31 mm²) and 10 AWG is 2.59 mm (5.26 mm²). Every 3 gauges doubles the copper area; every 6 gauges doubles the diameter.

AWG ↔ mm² converter

14121086421/0
Solid conductors drawn to the same scale. Going from 14 to 1/0 AWG multiplies the copper area by about 26.

American Wire Gauge chart, 4/0 to 40 AWG

AWGDiameter (in)Diameter (mm)Area (mm²)Area (cmil)Copper Ω/1000 ft @20 °C
4/00.460011.684107.22211,6000.0490
3/00.409610.40585.03167,8060.0618
2/00.36489.26667.43133,0770.0779
1/00.32498.25153.48105,5350.0983
10.28937.34842.4183,6930.1239
20.25766.54433.6366,3710.1563
30.22945.82726.6752,6350.1970
40.20435.18921.1541,7410.2485
50.18194.62116.7733,1020.3133
60.16204.11513.3026,2510.3951
70.14433.66510.5520,8180.4982
80.12853.2648.3716,5100.6282
90.11442.9066.6313,0930.7921
100.10192.5885.2610,3830.9988
110.09072.3054.178,2341.26
120.08082.0533.316,5301.59
130.07201.8282.625,1782.00
140.06411.6282.084,1072.53
150.05711.4501.653,2573.18
160.05081.2911.312,5834.02
170.04531.1501.042,0485.06
180.04031.0240.821,6246.38
190.03590.9120.651,2888.05
200.03200.8120.521,02210.15
210.02850.7230.4181012.80
220.02530.6440.3364216.14
230.02260.5730.2650920.36
240.02010.5110.2040425.67
250.01790.4550.1632032.37
260.01590.4050.1325440.81
270.01420.3610.1020251.47
280.01260.3210.081016064.90
290.01130.2860.064212781.83
300.01000.2550.0509101103.19
310.00890.2270.040480130.12
320.00800.2020.032063164.08
330.00710.1800.025450206.90
340.00630.1600.020140260.90
350.00560.1430.016032328.98
360.00500.1270.012725414.84
370.00450.1130.010020523.10
380.00400.1010.008016659.62
390.00350.0900.006312831.77
400.00310.0800.0050101048.84
Solid round conductors computed from the ASTM B258 definition, d = 0.005 in × 92^((36 − n)/39). Resistance uses annealed copper at 10.371 Ω·cmil/ft. Highlighted rows are the common household branch-circuit sizes.

d = 0.005 in × 92(36 − n)/39
area = (1000 × d)² cmil = π ÷ 4 × dmm² mm²
R = 10.371 × 1000 ÷ cmil Ω per 1000 ft (copper, 20 °C)

n is the gauge number, with 1/0 = 0, 2/0 = −1, 3/0 = −2 and 4/0 = −3. Every step of one gauge multiplies the diameter by about 1.123, so six steps double it and three steps double the area. The resistance column is for copper at room temperature; NEC Table 8 lists values at 75 °C, about 21% higher, and that is what the voltage drop calculator on this site uses.

Building wire: ampacity by gauge

For house wiring the question is usually how much current a gauge can carry. The answer depends on the insulation temperature rating and the terminals, which is why NEC Table 310.16 gives three columns. NM-B cable uses the 60 °C column.

SizeCu 60 °CCu 75 °CCu 90 °CAl 60 °CAl 75 °CAl 90 °C240.4(D) cap
14 AWG152025———15 A
12 AWG20253015202520 A
10 AWG30354025303530 A
8 AWG405055354045—
6 AWG556575405055—
4 AWG708595556575—
3 AWG85100115657585—
2 AWG951151307590100—
1 AWG11013014585100115—
1/0 AWG125150170100120135—
2/0 AWG145175195115135150—
3/0 AWG165200225130155175—
4/0 AWG195230260150180205—
Amperes, NEC 2023 Table 310.16: not more than three current-carrying conductors, 30 °C (86 °F) ambient. The last column is the largest breaker allowed on small copper conductors regardless of the table.

Sizes larger than 4/0 are named in kcmil (thousands of circular mils): 250, 300, 350, 400 and 500 kcmil are the common service and feeder sizes.

Metric cable sizes and the nearest AWG

Metric sizeExact AWGNearest standard
0.5 mm²20.1520 AWG
0.75 mm²18.4018 AWG
1 mm²17.1617 AWG
1.5 mm²15.4115 AWG
2.5 mm²13.2113 AWG
4 mm²11.1811 AWG
6 mm²9.439 AWG
10 mm²7.237 AWG
16 mm²5.205 AWG
25 mm²3.283 AWG
35 mm²1.832 AWG
50 mm²0.291/0 AWG
70 mm²-1.162/0 AWG
95 mm²-2.483/0 AWG
120 mm²-3.494/0 AWG
Computed from the cross-section. When the exact value falls between two gauges, a 2.5 mm² cable for instance sits between 14 and 13 AWG, choose the size with the larger area for current-carrying work.

Which gauge for which job

Typical sizes in US homes and on job sites. They assume copper, short runs and the circuit breaker shown; long runs go one or two sizes up for voltage drop.

UseTypical gaugeNotes
Lamp and appliance cords18 or 16 AWGCord ampacity follows Table 400.5, not 310.16
Thermostat and doorbell wire18 AWGClass 2 low-voltage, 24 V
Light-duty extension cord16 AWGUp to about 10–13 A at 25–50 ft
Lighting and general outlets, 15 A14 AWG14-2 NM-B, white jacket
Kitchen, bath, laundry outlets, 20 A12 AWG12-2 NM-B, yellow jacket
Dryer or water heater, 30 A10 AWG10-3 for dryers with a neutral
Cooktop or 40 A charger8 AWG8 AWG NM-B is a 40 A cable
Range, 50 A charger6 AWG50 amp wire size
100 A subpanel feeder3 AWG Cu or 1 AWG AlAt 75 °C, before voltage drop
200 A residential service2/0 Cu or 4/0 AlUsing the 310.12 dwelling reduction
Common practice, not a substitute for sizing the actual circuit with the calculator.

How gauge changes resistance and current

Because area changes by a fixed ratio between gauges, resistance does too: each step down in gauge number cuts resistance by about 20.6%, and each three steps cut it in half. That is why a 10 AWG run has roughly 63% of the resistance of 12 AWG and can carry the same load almost 60% farther for the same voltage drop. Ampacity does not scale so neatly, because a thicker conductor sheds heat through a surface that grows more slowly than its area; this is why the NEC table rises in uneven steps rather than doubling every three gauges.

Solid vs stranded

A stranded conductor of a given AWG has the same total copper area as the solid one, so ampacity is the same and resistance nearly so: NEC Table 8 lists 12 AWG copper at 1.93 Ω/1000 ft solid and 1.98 stranded. Stranded wire is larger in overall diameter and much more flexible, which is why it is required for 8 AWG and larger in conduit under 310.3(C) and preferred for anything that moves or vibrates.

Reading the gauge on a cable

NM-B jackets are color-coded by size in the US: white for 14 AWG, yellow for 12 AWG, orange for 10 AWG, and black for 8 and 6 AWG. The printed legend gives the full story: "12-2 W/G" means two 12 AWG insulated conductors plus a bare ground; "10-3" adds a red conductor for 240 V or multi-wire circuits.

Related calculators and charts

Questions people ask

Why does a smaller AWG number mean a thicker wire?

The gauge number counted the drawing steps used to make the wire. Each pass through a die made it thinner, so a higher number meant more passes and a thinner wire. The modern standard (ASTM B258) fixes 36 AWG at 0.005 in and 0000 AWG at 0.46 in, with 39 equal ratio steps between them.

How thick is 12 gauge wire?

Solid 12 AWG copper is 0.0808 in (2.05 mm) across with an area of 3.31 mm². Stranded 12 AWG has the same copper area but is a little larger overall because of the gaps between strands.

What is the rule of thumb between gauges?

Every 3 gauge numbers doubles or halves the area (and the resistance), and every 6 numbers doubles or halves the diameter. Every 10 numbers changes the area by about 10 times.

Is AWG the same as SWG or mm²?

No. SWG (British Standard Wire Gauge) uses different steps, and most of the world sizes cable by cross-section in mm². Use the metric table on this page to find the nearest AWG size, and pick the larger one when the match is not exact.

Does this chart tell me how many amps a wire can carry?

The full chart gives geometry and resistance only. For building wire, use the ampacity table further down, which comes from NEC Table 310.16 and depends on the insulation temperature rating.