Wire Size Calculator

Enter the current, voltage and one-way distance. The calculator checks NEC ampacity, the small-conductor breaker limits and voltage drop, then tells you which one set the size.

Quick answer: 14 AWG copper for 15 A, 12 AWG for 20 A, 10 AWG for 30 A. Past about 46 ft on a 20 A, 120 V circuit, voltage drop rather than the breaker decides the size, and you move up one gauge.

Wire size calculator

Wire size by breaker: the short table

This is the minimum copper or aluminum size for each common breaker before you account for distance. NM-B cable is limited to the 60 °C column by NEC 334.80, while individual THHN conductors in conduit can use 75 °C when every terminal in the circuit is rated 75 °C.

BreakerCopper NM-B (60 °C)Copper THHN (75 °C)Aluminum (75 °C)
15 A14 AWG14 AWG12 AWG
20 A12 AWG12 AWG10 AWG
30 A10 AWG10 AWG8 AWG
40 A8 AWG8 AWG8 AWG
50 A6 AWG8 AWG6 AWG
60 A4 AWG6 AWG4 AWG
70 A4 AWG4 AWG3 AWG
80 A3 AWG4 AWG2 AWG
100 A1 AWG3 AWG1 AWG
125 A1/0 AWG1 AWG2/0 AWG
150 A3/0 AWG1/0 AWG3/0 AWG
200 A250 kcmil3/0 AWG250 kcmil
Minimum sizes from NEC Table 310.16 and the 240.4(D) small-conductor limits. Add length in the calculator above to check voltage drop.

How the calculator chooses a size

Every result passes three checks, in this order, and the calculator reports which one set the size.

  1. Ampacity. The conductor's allowable current from Table 310.16 in the temperature column that matches your cable. For a continuous load (one that runs three hours or more) the wire must carry 125% of that load, per 210.19(A)(1) for branch circuits and 215.2(A)(1) for feeders.
  2. Small-conductor limits. 14, 12 and 10 AWG copper may not be protected above 15, 20 and 30 A, even though the table lists higher numbers. Aluminum 12 and 10 AWG stop at 15 and 25 A.
  3. Voltage drop. Using the DC resistance from Chapter 9 Table 8, the calculator works out the volts lost in the run and steps up until the drop is at or below your target: 3% for a branch circuit is the usual design figure, 5% for feeder plus branch combined.

The answer is the smallest size that clears all three. If the drop check forced it up, you see a note saying so, which is the part most quick charts leave out.

Which temperature column applies to you

Table 310.16 lists three ampacities for each size, and choosing the wrong one is the most common sizing mistake.

Worked example: a 40 A EV charger in the garage

A Level 2 charger drawing 40 A is a continuous load, so the wire is sized for 40 × 1.25 = 50 A on a 50 A breaker. With an 80 ft run at 240 V:

The distance is short enough that ampacity decides. Compare a 20 A, 120 V outlet circuit run 120 ft to a detached shed: the breaker alone says 12 AWG, but the drop check pushes it to 6 AWG so the far outlet still sees 117.6 V under full load.

Copper or aluminum

Copper is the default for 15–60 A branch circuits: it is smaller for the same current, easier to terminate on receptacles and switches, and less sensitive to loose connections. Aluminum (AA-8000 series alloy) is the normal choice for service entrance cable, feeders to subpanels and long runs where copper would cost two to three times more. Use lugs and breakers marked AL/CU, apply anti-oxidant compound where the manufacturer calls for it, and torque connections to the listed value.

What this calculator does not cover

Codes are adopted locally and many jurisdictions amend them. Treat these numbers as a design check and confirm with your inspector or a licensed electrician before you pull wire.

Related calculators and charts

Questions people ask

What size wire do I need for a 20 amp circuit?

12 AWG copper. The table allows 25 A for 12 AWG at 75 °C, but NEC 240.4(D) caps it at a 20 A breaker. On a 120 V circuit that 12 AWG run reaches 3% voltage drop at about 46 ft of full load, so long runs to a shed or garage often use 10 AWG.

Should I size wire by the breaker or by the load?

By both. The breaker protects the wire, so the wire ampacity should normally be at least the breaker rating. NEC 240.4(B) lets you round up to the next standard breaker when the ampacity falls between ratings, but not on multi-outlet circuits for plug-in loads and never past the 240.4(D) small-conductor limits. Then check the real load for voltage drop over the actual distance.

Is the length one-way or round trip?

Enter the one-way distance from the panel to the load. The formula already doubles it for the hot and the return conductor on single-phase and DC circuits.

Why does the calculator pick a bigger wire than the chart?

Because the run is long enough that the smaller wire would drop more than the voltage limit you chose. The chart only answers how much current the wire can carry without overheating; it says nothing about distance.

Can I use the 90 °C column for THHN?

Only as a starting point for derating (hot attics, more than three current-carrying conductors in a conduit). The final ampacity is limited by the temperature rating of the breaker and device terminals, which is 60 °C or 75 °C in almost every home.

Does aluminum wire need to be bigger?

Yes. Aluminum carries roughly 78% of the current of the same copper size and has about 1.6 times the resistance, so it usually goes up two gauge sizes. It is common and code-compliant for feeders and service entrance cable, rarely used for 15–20 A branch circuits.