Wire Size Calculator
Enter the current, voltage and one-way distance. The calculator checks NEC ampacity, the small-conductor breaker limits and voltage drop, then tells you which one set the size.
Quick answer: 14 AWG copper for 15 A, 12 AWG for 20 A, 10 AWG for 30 A. Past about 46 ft on a 20 A, 120 V circuit, voltage drop rather than the breaker decides the size, and you move up one gauge.
Wire size calculator
Wire size by breaker: the short table
This is the minimum copper or aluminum size for each common breaker before you account for distance. NM-B cable is limited to the 60 °C column by NEC 334.80, while individual THHN conductors in conduit can use 75 °C when every terminal in the circuit is rated 75 °C.
| Breaker | Copper NM-B (60 °C) | Copper THHN (75 °C) | Aluminum (75 °C) |
|---|---|---|---|
| 15 A | 14 AWG | 14 AWG | 12 AWG |
| 20 A | 12 AWG | 12 AWG | 10 AWG |
| 30 A | 10 AWG | 10 AWG | 8 AWG |
| 40 A | 8 AWG | 8 AWG | 8 AWG |
| 50 A | 6 AWG | 8 AWG | 6 AWG |
| 60 A | 4 AWG | 6 AWG | 4 AWG |
| 70 A | 4 AWG | 4 AWG | 3 AWG |
| 80 A | 3 AWG | 4 AWG | 2 AWG |
| 100 A | 1 AWG | 3 AWG | 1 AWG |
| 125 A | 1/0 AWG | 1 AWG | 2/0 AWG |
| 150 A | 3/0 AWG | 1/0 AWG | 3/0 AWG |
| 200 A | 250 kcmil | 3/0 AWG | 250 kcmil |
How the calculator chooses a size
Every result passes three checks, in this order, and the calculator reports which one set the size.
- Ampacity. The conductor's allowable current from Table 310.16 in the temperature column that matches your cable. For a continuous load (one that runs three hours or more) the wire must carry 125% of that load, per 210.19(A)(1) for branch circuits and 215.2(A)(1) for feeders.
- Small-conductor limits. 14, 12 and 10 AWG copper may not be protected above 15, 20 and 30 A, even though the table lists higher numbers. Aluminum 12 and 10 AWG stop at 15 and 25 A.
- Voltage drop. Using the DC resistance from Chapter 9 Table 8, the calculator works out the volts lost in the run and steps up until the drop is at or below your target: 3% for a branch circuit is the usual design figure, 5% for feeder plus branch combined.
The answer is the smallest size that clears all three. If the drop check forced it up, you see a note saying so, which is the part most quick charts leave out.
Which temperature column applies to you
Table 310.16 lists three ampacities for each size, and choosing the wrong one is the most common sizing mistake.
- 60 °C: NM-B (Romex) and UF-B cable in a house, and any circuit whose breaker or device terminals are rated 60 °C. Under 110.14(C), equipment rated 100 A or less, or wired with 14 through 1 AWG, defaults to 60 °C unless it is marked 75 °C.
- 75 °C: THHN/THWN-2 conductors in conduit, SER and other feeder cables, when the breaker and lugs carry a 60/75 °C or 75 °C marking. Most modern residential breakers are marked 60/75 °C.
- 90 °C: only for derating. If a conduit holds more than three current-carrying conductors or passes through a hot rooftop, you start from the 90 °C number, apply the correction factors, and the result may not exceed the 75 °C or 60 °C value of the terminals.
Worked example: a 40 A EV charger in the garage
A Level 2 charger drawing 40 A is a continuous load, so the wire is sized for 40 × 1.25 = 50 A on a 50 A breaker. With an 80 ft run at 240 V:
- THHN copper in conduit at 75 °C: 8 AWG, voltage drop 4.98 V (2.07%).
- NM-B copper at 60 °C: 6 AWG, voltage drop 3.14 V (1.31%).
The distance is short enough that ampacity decides. Compare a 20 A, 120 V outlet circuit run 120 ft to a detached shed: the breaker alone says 12 AWG, but the drop check pushes it to 6 AWG so the far outlet still sees 117.6 V under full load.
Copper or aluminum
Copper is the default for 15–60 A branch circuits: it is smaller for the same current, easier to terminate on receptacles and switches, and less sensitive to loose connections. Aluminum (AA-8000 series alloy) is the normal choice for service entrance cable, feeders to subpanels and long runs where copper would cost two to three times more. Use lugs and breakers marked AL/CU, apply anti-oxidant compound where the manufacturer calls for it, and torque connections to the listed value.
What this calculator does not cover
- Ambient temperature correction (Table 310.15(B)(1)) and adjustment for more than three current-carrying conductors (Table 310.15(C)(1)).
- The 310.12 dwelling service and feeder table that allows smaller conductors for 120/240 V services.
- Motor circuits, which are sized from Article 430 full-load current tables, and HVAC equipment, which uses the nameplate MCA and MOCP.
Codes are adopted locally and many jurisdictions amend them. Treat these numbers as a design check and confirm with your inspector or a licensed electrician before you pull wire.
Related calculators and charts
- Voltage drop calculatorVolts lost over any run, copper or aluminum, single- or three-phase.
- AWG wire gauge chartDiameter, mm², resistance and ampacity from 4/0 to 40 AWG.
- What size wire for 50 ampRanges, EV chargers, subpanels and RV pedestals, by distance.
Questions people ask
What size wire do I need for a 20 amp circuit?
12 AWG copper. The table allows 25 A for 12 AWG at 75 °C, but NEC 240.4(D) caps it at a 20 A breaker. On a 120 V circuit that 12 AWG run reaches 3% voltage drop at about 46 ft of full load, so long runs to a shed or garage often use 10 AWG.
Should I size wire by the breaker or by the load?
By both. The breaker protects the wire, so the wire ampacity should normally be at least the breaker rating. NEC 240.4(B) lets you round up to the next standard breaker when the ampacity falls between ratings, but not on multi-outlet circuits for plug-in loads and never past the 240.4(D) small-conductor limits. Then check the real load for voltage drop over the actual distance.
Is the length one-way or round trip?
Enter the one-way distance from the panel to the load. The formula already doubles it for the hot and the return conductor on single-phase and DC circuits.
Why does the calculator pick a bigger wire than the chart?
Because the run is long enough that the smaller wire would drop more than the voltage limit you chose. The chart only answers how much current the wire can carry without overheating; it says nothing about distance.
Can I use the 90 °C column for THHN?
Only as a starting point for derating (hot attics, more than three current-carrying conductors in a conduit). The final ampacity is limited by the temperature rating of the breaker and device terminals, which is 60 °C or 75 °C in almost every home.
Does aluminum wire need to be bigger?
Yes. Aluminum carries roughly 78% of the current of the same copper size and has about 1.6 times the resistance, so it usually goes up two gauge sizes. It is common and code-compliant for feeders and service entrance cable, rarely used for 15–20 A branch circuits.